Commercial and Industrial Reverse Osmosis Systems – 18,000 up to 86,400 GPD
Electricity is the most expensive cost of commercial and industrial reverse osmosis systems. The pumps utilized on the AmeriWater HRO series of commercial and industrial reverse osmosis systems use the highest efficiency Class I (EFFI) motors, resulting in reduced energy consumption and consequently reduced operating costs. In addition, the FILMTECTM high productivity, low energy membranes utilized require less pressure to function. Large 34-mil spacer optimized for pressure drop minimization reduces the impact of fouling and enhances the cleaning efficiency. The iLECTM technology (interlocking connectors) enables sustained higher quality permeate throughout the life of the element by dramatically reducing the potential for seal leakage and reduces energy consuming flow resistance, resulting in lower operating costs.
Features
- Pump with high efficiency Class I (EFFI) motor
- High productivity, low energy membranes
- Horizontal or vertical configuration
- Interlocking connectors (iLECTM) technology
- One micron stainless steel cartridge prefilter
- Powder coated aluminum frame
- Product flow meter
- Concentrate reject flow meter with valve
- Stainless liquid filled pressure gauges for prefilter, post filter, pump, and reject
- Sample ports on each vessel
- Digital microprocessor with current hours, conductivity, % rejection, temperature, tank high and l ow contacts, pretreat lockout, alarm contacts, low feed PSI alarm, and high conductivity alarm
- Automatic inlet shut off valve
Specifications
- Design Temperature: 77°F
- Operation Temperature: 50 – 90°F
- Minimum Inlet Pressure: 20 PSI
- Nominal Rejection: 95 – 98%
- Recovery: 50 – 75% (adjustable)
- Pump Operation PSI: 180 – 225
Gallons per day* | 18,000 | 57,600 | 64,800 | 86,400 |
Product Flow GPM* | 12.5 | 40 | 45 | 60 |
Number of Membranes | 2 | 8 | 9 | 12 |
Array | 1-1 | 2-2 | 2-1 | 2-2 |
Configuration | Vertical | Horizontal | ||
Pump HP, 3 Ph | 5 | 15 | ||
FLA 230V | 15.2 | 42 | ||
FLA 460V | 7.6 | 21 | ||
FLA 575V | 6.1 | 17 | ||
Shipping Weight | 915 | 2,800 | 2,950 | 3,300 |
Dimensions In. (W x D x H) | 55 X 28 X 75 | 108 X 32 X 72 | 148 X 32 X 72 | |
* Permeate flow based on the following standard test conditions: 2000 ppm NaCl, 150 psi, 77F, pH 8 and 15% recovery. A complete water analysis and computer modeling is necessary for an accurate permeate flow. | ||||
Model numbers begin with 00HRO then the gallons. Examples: 00HRO18000 or 00HRO576000 |